Power Factor Correction Calculator
Load Profile
Active Power (P)
kW
System Voltage (V
LL
)
V
Power Factor Targets
Current PF (cos φ
1
)
(Lagging, typically 0.6 - 0.9)
Target PF (cos φ
2
)
Capacitor Bank Step Size
Auto / Total Only
12.5 kVAr
25 kVAr
50 kVAr
100 kVAr
Correction Required
Required Capacitor (Q
c
)
- kVAr
Suggested Bank
-
System Benefits
Current Before (I
1
)
- A
Current After (I
2
)
- A
Current Reduction
- %
π Export Report
π Reset
*Calculates required reactive power (kVAr) to improve PF. Results assume balanced 3-Phase system.
Technical Notes & Engineering Logic
Variable Definitions
P (kW):
Active/Real Power doing useful work.
Q
c
(kVAr):
Capacitor Reactive Power required.
cos φ
1
:
Initial (Uncorrected) Power Factor.
cos φ
2
:
Target Power Factor.
Formulas
Capacitor Sizing:
Q
c
= P × [tan(acos(PF
1
)) - tan(acos(PF
2
))]
Line Current (3φ):
I = (P × 1000) / (√3 × V × PF)
Apparent Power:
S (kVA) = P / PF
Assumptions & Warnings
Assumes a standard inductive load (Lagging PF).
Does not account for Harmonic Resonance. If Total Harmonic Distortion (THD) is high, Detuned Reactors are required.
Calculations assume voltage remains constant.